97国产看片免费人成视频_卡通动漫日韩一三区_韩国三级中文字幕hd在线_国产成人综合网高清_色偷偷男人的天堂亚洲av_乱爱性全过程免费视频午夜_久久多多屋影院三级_日韩高清在线看AV片_久亚洲第一综合天堂另类专_国产一级男女牲交高潮大片

Hotline: +86-021-57278880
Language:   
Your current location: ProductsHydraulic Control ValveWire Mouth Backflow Preventer

HS11X-16T Wire Mouth Backflow Preventer

Product overview

Product model: HS11X-16T
Nominal diameter: DN40~100mm
Nominal pressure: PN1.0~1.6MPa
Applicable temperature: 0~80℃ (up to 200℃ if necessary)
Flange standard: GB/T17241.6, GB/T9113
Test standard: GB/T 13927, API598

HS11X-16T Wire Mouth Backflow Preventer product details

HS11X-16T Wire Mouth Backflow Preventer product description:
HS11X-16T silk mouth backflow preventer is to repair the pipeline and power, the tap water is often interrupted, once the power supply is restored, tap water becomes yellow and dirty, it is due to the process of water, from the fire pipe , Unoccupied buildings or water pipes have not yet used the branch of the backwater, rust water back. In order to allow residents to drink clean water, backflow preventer this device can effectively prevent the occurrence of dirty water in the above circumstances, not only ensure the safety of residents drinking water, but also save water resources. According to the introduction of China Building Standard Design Institute, the Ministry of Construction has revised the relevant national standards and installed "backflow preventer" on the building water supply pipelines.  


HS11X-16T Wire Mouth Backflow Preventere product structure:
Backflow prevention device is composed of two levels of back-stop system and a drainage pressure relief system. The drainage pressure relief system upper chamber is connected with the inlet end of the first-stage check-back system. 
The first and second-level check-back system is mainly composed of the valve body, inlet joint, disc, gaskets, springs and so on. 
Drainage pressure relief system is mainly composed of valve cover, diaphragm, valve core, gaskets, drain, spring, air baffle, etc. The outlet of air baffle must be connected to the drainage pipe network or sewer.


HS11X-16T Wire Mouth Backflow Preventer working principle:
Backflow prevention device is added in the secondary checkback system, a drainage pressure relief device, so that even if the secondary check seal at the same time damage, it can also play a role in preventing backflow pollution. Its working principle: 
1. Normal water supply: 
a. Clean municipal water from the first-class check-back system through the drain to the second-level check-back system to export water to users, the first-level check-in system to import high-pressure water into the drainage diaphragm Cavity, and the diaphragm under the cavity and the first stage check valve outlet (second stage check valve inlet) communicating, due to its existence of a certain pressure difference ΔP1 = 0.035MPa, pushing the valve flap down, drain closed, backflow preventer Normal water supply; 
b. When the valve after the pipeline without users, water still. Such as the inlet pressure remains unchanged, there is pressure before and after the drain is still closed, such as the inlet pressure drops, the intermediate chamber and the valve differential pressure ΔP1 ≤ 0.022MPa, then the drainage control spring to open the spool, open the drain Allow the middle chamber to drain, keeping ΔP1 at 0.035 MPa. 
 
2. seal failure: 
a. Backflow preventer after the pipe network pressure rises above the valve inlet pressure, such as the second check valve seal intact, high-pressure water will not backflow, the diaphragm up and down to maintain the original pressure Poor, drain closed, no pressure relief. When the second check valve seal leak damage, the second check valve before the pressure increases, resulting in lower diaphragm pressure drop across the drain, drain open, drain pressure relief; this time, such as the first stop Check valve seal damage at the same time, as the second-stage check valve back to the high-pressure water has been decompression, it will not back to the first-class check valve. 
b. When the valve pressure is higher than the pressure before the valve, such as water pressure continues to decline, the pressure on the diaphragm diaphragm pressure drop, the safety control valve to open the drainage spring drainage regulator drainage. When the inlet pressure drops to zero or negative pressure, the drain opens completely, the water is drained and the air enters the vacuum chamber through the drain to prevent siphon backflow.
 
3. The valve opening pressure ≤ 0.07MPa, the specification provides in the range of 0.06 ~ 0.1MPa, inlet check valve working pressure is 0.035MPa. 
 
HS11X-16T Wire Mouth Backflow Preventer main shape and installation size:

Specification DN (mm)

Total length

Inlet and outlet pipe diameter (in)

Drainage pipe diameter (in)

Weight (kg)

DN15

169

1/2

1/2

1.2

DN20

172

3/4

1/2

1.4

DN25

236

1

1/2

3.5

DN32

321

11/4

3/4

7

DN40

321

11/2

3/4

7

DN50

321

2

1

10



Reminder:

All text, data and pictures in this article are for reference only.To see more details of the HS11X-16T Wire Mouth Backflow Preventer performance parameters, structural dimension parameters, pricing, etc., or to request high quality printing samples, please Contact us.

Previous:Basket Filter
+86-021-57278881
qrCode